Wire Size for 100 Amp 200 Feet (120V)

StandardWire SizeAmpacityVolt DropDrop %
NEC (US)AWG 3/0 (85 mm²)200 A3.01 V2.51%
IEC (EU)95 mm²223 A2.69 V2.24%
BS (UK)50 mm²144 A5.11 V4.26%
AS/NZS50 mm²144 A5.11 V4.26%

About AWG 3/0

Typical use
165–200 A service entrance — standard 200 A residential service
Max breaker
200 A
Temperature rating
75 °C
NEC reference
NEC Table 310.16

Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.

Adjacent Current Comparison

CurrentAWGmm²AmpacityDrop %
60 AAWG 1/053.5 mm²150 A2.39%
100 AAWG 3/085 mm²200 A2.51%
150 AAWG 4/0107.2 mm²230 A2.98%

Adjacent Distance Comparison

DistanceAWGmm²AmpacityDrop %
150 ftAWG 1/053.5 mm²150 A2.99%
200 ftAWG 3/085 mm²200 A2.51%
300 ftAWG 4/0107.2 mm²230 A2.98%