Wire Size for 15 Amp 300 Feet (120V)
| Standard | Wire Size | Ampacity | Volt Drop | Drop % |
| NEC (US) | AWG 4 (21.2 mm²) | 85 A | 2.71 V | 2.26% |
| IEC (EU) | 16 mm² | 76 A | 3.59 V | 3.00% |
| BS (UK) | 10 mm² | 57 A | 5.75 V | 4.79% |
| AS/NZS | 10 mm² | 57 A | 5.75 V | 4.79% |
About AWG 4
- Typical use
- 70–85 A feeders — sub-panel feeds, commercial equipment
- Max breaker
- 85 A
- Temperature rating
- 75 °C
- NEC reference
- NEC Table 310.16
Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.
Adjacent Current Comparison
| Current | AWG | mm² | Ampacity | Drop % |
| 15 A | AWG 4 | 21.2 mm² | 85 A | 2.26% |
| 20 A | AWG 3 | 26.7 mm² | 100 A | 2.39% |
Adjacent Distance Comparison
| Distance | AWG | mm² | Ampacity | Drop % |
| 200 ft | AWG 6 | 13.3 mm² | 65 A | 2.40% |
| 300 ft | AWG 4 | 21.2 mm² | 85 A | 2.26% |