Wire Size for 15 Amp 75 Feet (120V)

StandardWire SizeAmpacityVolt DropDrop %
NEC (US)AWG 10 (5.26 mm²)35 A2.73 V2.28%
IEC (EU)4 mm²32 A3.59 V3.00%
BS (UK)2.5 mm²24 A5.75 V4.79%
AS/NZS2.5 mm²24 A5.75 V4.79%

About AWG 10

Typical use
30 A circuits — clothes dryers, window A/C units, water heaters
Max breaker
30 A
Temperature rating
60 °C
NEC reference
NEC 240.4(D)(1)

Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.

Adjacent Current Comparison

CurrentAWGmm²AmpacityDrop %
15 AAWG 105.26 mm²35 A2.28%
20 AAWG 88.37 mm²50 A1.91%

Adjacent Distance Comparison

DistanceAWGmm²AmpacityDrop %
50 ftAWG 123.31 mm²25 A2.41%
75 ftAWG 105.26 mm²35 A2.28%
100 ftAWG 88.37 mm²50 A1.91%