Wire Size for 150 Amp 150 Feet (120V)

StandardWire SizeAmpacityVolt DropDrop %
NEC (US)AWG 3/0 (85 mm²)200 A3.38 V2.82%
IEC (EU)95 mm²223 A3.03 V2.52%
BS (UK)70 mm²184 A4.11 V3.42%
AS/NZS70 mm²184 A4.11 V3.42%

About AWG 3/0

Typical use
165–200 A service entrance — standard 200 A residential service
Max breaker
200 A
Temperature rating
75 °C
NEC reference
NEC Table 310.16

Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.

Adjacent Current Comparison

CurrentAWGmm²AmpacityDrop %
100 AAWG 1/053.5 mm²150 A2.99%
150 AAWG 3/085 mm²200 A2.82%
200 AAWG 4/0107.2 mm²230 A2.98%

Adjacent Distance Comparison

DistanceAWGmm²AmpacityDrop %
100 ftAWG 1/053.5 mm²150 A2.99%
150 ftAWG 3/085 mm²200 A2.82%
200 ftAWG 4/0107.2 mm²230 A2.98%