Wire Size for 30 Amp 100 Feet (120V)
| Standard | Wire Size | Ampacity | Volt Drop | Drop % |
| NEC (US) | AWG 6 (13.3 mm²) | 65 A | 2.88 V | 2.40% |
| IEC (EU) | 16 mm² | 76 A | 2.40 V | 2.00% |
| BS (UK) | 10 mm² | 57 A | 3.83 V | 3.20% |
| AS/NZS | 10 mm² | 57 A | 3.83 V | 3.20% |
About AWG 6
- Typical use
- 55–65 A circuits — sub-panels, large appliances, EV chargers (Level 2)
- Max breaker
- 65 A
- Temperature rating
- 75 °C
- NEC reference
- NEC Table 310.16
Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.
Adjacent Current Comparison
| Current | AWG | mm² | Ampacity | Drop % |
| 20 A | AWG 8 | 8.37 mm² | 50 A | 2.55% |
| 30 A | AWG 6 | 13.3 mm² | 65 A | 2.40% |
| 40 A | AWG 4 | 21.2 mm² | 85 A | 2.01% |
Adjacent Distance Comparison
| Distance | AWG | mm² | Ampacity | Drop % |
| 75 ft | AWG 8 | 8.37 mm² | 50 A | 2.86% |
| 100 ft | AWG 6 | 13.3 mm² | 65 A | 2.40% |
| 150 ft | AWG 4 | 21.2 mm² | 85 A | 2.26% |