Wire Size for 40 Amp 75 Feet (120V)

StandardWire SizeAmpacityVolt DropDrop %
NEC (US)AWG 6 (13.3 mm²)65 A2.88 V2.40%
IEC (EU)16 mm²76 A2.40 V2.00%
BS (UK)10 mm²57 A3.83 V3.20%
AS/NZS10 mm²57 A3.83 V3.20%

About AWG 6

Typical use
55–65 A circuits — sub-panels, large appliances, EV chargers (Level 2)
Max breaker
65 A
Temperature rating
75 °C
NEC reference
NEC Table 310.16

Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.

Adjacent Current Comparison

CurrentAWGmm²AmpacityDrop %
30 AAWG 88.37 mm²50 A2.86%
40 AAWG 613.3 mm²65 A2.40%
50 AAWG 421.2 mm²85 A1.88%

Adjacent Distance Comparison

DistanceAWGmm²AmpacityDrop %
50 ftAWG 88.37 mm²50 A2.55%
75 ftAWG 613.3 mm²65 A2.40%
100 ftAWG 421.2 mm²85 A2.01%