Wire Size for 50 Amp 150 Feet (120V)

StandardWire SizeAmpacityVolt DropDrop %
NEC (US)AWG 3 (26.7 mm²)100 A3.59 V2.99%
IEC (EU)35 mm²119 A2.74 V2.28%
BS (UK)16 mm²76 A5.99 V4.99%
AS/NZS16 mm²76 A5.99 V4.99%

About AWG 3

Typical use
85–100 A feeders — large sub-panels, commercial branch circuits
Max breaker
100 A
Temperature rating
75 °C
NEC reference
NEC Table 310.16

Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.

Adjacent Current Comparison

CurrentAWGmm²AmpacityDrop %
40 AAWG 326.7 mm²100 A2.39%
50 AAWG 326.7 mm²100 A2.99%
60 AAWG 233.6 mm²115 A2.85%

Adjacent Distance Comparison

DistanceAWGmm²AmpacityDrop %
100 ftAWG 421.2 mm²85 A2.51%
150 ftAWG 326.7 mm²100 A2.99%
200 ftAWG 142.4 mm²130 A2.51%