Wire Size for 50 Amp 300 Feet (120V)

StandardWire SizeAmpacityVolt DropDrop %
NEC (US)AWG 1/0 (53.5 mm²)150 A3.58 V2.99%
IEC (EU)70 mm²184 A2.74 V2.28%
BS (UK)35 mm²119 A5.48 V4.56%
AS/NZS35 mm²119 A5.48 V4.56%

About AWG 1/0

Typical use
125–150 A service entrance — residential main service
Max breaker
150 A
Temperature rating
75 °C
NEC reference
NEC Table 310.16

Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.

Adjacent Current Comparison

CurrentAWGmm²AmpacityDrop %
40 AAWG 1/053.5 mm²150 A2.39%
50 AAWG 1/053.5 mm²150 A2.99%
60 AAWG 2/067.4 mm²175 A2.84%

Adjacent Distance Comparison

DistanceAWGmm²AmpacityDrop %
200 ftAWG 142.4 mm²130 A2.51%
300 ftAWG 1/053.5 mm²150 A2.99%