Wire Size for 50 Amp 75 Feet (120V)

StandardWire SizeAmpacityVolt DropDrop %
NEC (US)AWG 4 (21.2 mm²)85 A2.26 V1.88%
IEC (EU)16 mm²76 A3.00 V2.50%
BS (UK)10 mm²57 A4.79 V3.99%
AS/NZS10 mm²57 A4.79 V3.99%

About AWG 4

Typical use
70–85 A feeders — sub-panel feeds, commercial equipment
Max breaker
85 A
Temperature rating
75 °C
NEC reference
NEC Table 310.16

Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.