Wire Size for 60 Amp 75 Feet (120V)

StandardWire SizeAmpacityVolt DropDrop %
NEC (US)AWG 4 (21.2 mm²)85 A2.71 V2.26%
IEC (EU)16 mm²76 A3.59 V3.00%
BS (UK)16 mm²76 A3.59 V3.00%
AS/NZS16 mm²76 A3.59 V3.00%

About AWG 4

Typical use
70–85 A feeders — sub-panel feeds, commercial equipment
Max breaker
85 A
Temperature rating
75 °C
NEC reference
NEC Table 310.16

Always verify local code requirements. Wire sizing depends on insulation type, ambient temperature, and conduit fill.

Adjacent Current Comparison

CurrentAWGmm²AmpacityDrop %
50 AAWG 421.2 mm²85 A1.88%
60 AAWG 421.2 mm²85 A2.26%
100 AAWG 326.7 mm²100 A2.99%

Adjacent Distance Comparison

DistanceAWGmm²AmpacityDrop %
50 ftAWG 613.3 mm²65 A2.40%
75 ftAWG 421.2 mm²85 A2.26%
100 ftAWG 326.7 mm²100 A2.39%