AS/NZS 3000 Wire Sizing Guide: Australian & New Zealand Wiring Rules
How to size cables under the Wiring Rules using AS/NZS 3008.1, maximum demand, and voltage drop calculations
AS/NZS 3000 (commonly called the Wiring Rules) is the joint Australian and New Zealand standard for electrical installations. Cable sizing is performed using the companion standard AS/NZS 3008.1 (Selection of cables), which provides current-carrying capacity tables for various installation conditions. This guide explains the cable sizing methodology, voltage drop requirements, and key differences from other international standards.
Overview of AS/NZS 3000
AS/NZS 3000 is published jointly by Standards Australia and Standards New Zealand. It covers installations operating at voltages up to 1000 V AC or 1500 V DC. The standard is legally referenced in Australian state and territory electrical safety legislation, making compliance mandatory. Licensed electricians in Australia and New Zealand must demonstrate competence in its application. The current edition (2018, Amendment 2:2021) aligns closely with IEC 60364 but includes region-specific requirements for harsh climates, underground installations, and solar PV systems.
Cable Sizing with AS/NZS 3008.1
AS/NZS 3008.1 provides current-carrying capacity tables for copper and aluminium conductors. The process is: (1) Determine design current from maximum demand (AS/NZS 3000 Section 2). (2) Apply derating factors for ambient temperature, grouping, soil thermal resistivity (buried cables), and depth of burial. (3) Select a cable with derated ampacity ≥ design current. (4) Check voltage drop. The standard sizes follow IEC: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm².
Current-Carrying Capacity Tables
For single-phase copper PVC cables installed in air (clipped to surface), AS/NZS 3008.1 Table 3 gives: 1.5 mm² = 17.5 A, 2.5 mm² = 24 A, 4 mm² = 32 A, 6 mm² = 41 A, 10 mm² = 57 A, 16 mm² = 76 A, 25 mm² = 97 A. These values assume an ambient temperature of 40 °C (not 30 °C as in IEC), reflecting the hotter Australian climate. For XLPE cables, ampacities are higher: 2.5 mm² = 33 A, 4 mm² = 44 A, 6 mm² = 56 A.
Voltage Drop: 5% Maximum
AS/NZS 3000 Clause 3.6.2 limits voltage drop to 5% between the point of supply and the furthest point of the installation. Unlike IEC/BS which split 3% lighting / 5% power, AS/NZS uses a single 5% limit for all circuit types. The formula uses cable impedance values from AS/NZS 3008.1 Table 35 (mV/A/m). For 2.5 mm² single-phase PVC cable: 18.1 mV/A/m. Voltage drop: ΔU = mV/A/m × I × L / 1000. At 230 V, 5% = 11.5 V maximum. For 20 A over 25 m: ΔU = 18.1 × 20 × 25 / 1000 = 9.05 V = 3.9%.
Maximum Demand Calculation
AS/NZS 3000 Section 2 provides methods for calculating maximum demand, which determines the design current for sub-mains and the main switchboard. For residential installations, diversity factors are applied: first 10 A of lighting at 100%, remainder at 50%; power points use a lookup table based on the number of outlets. Air conditioning and fixed appliance loads are added at full rating. The total maximum demand determines the main switch and sub-main cable size. This differs from NEC Article 220, which uses different demand factors.
RCD and Safety Switch Requirements
AS/NZS 3000 requires 30 mA RCD protection (called safety switches in Australia) for all final sub-circuits of a domestic installation, including lighting, socket outlets, and fixed appliances. This goes further than BS 7671, which exempts some circuits. In New Zealand, the requirements are slightly different, with RCDs required for socket outlets and circuits likely to supply outdoor equipment. All RCDs must be tested every 6 months by the user (push-button test) and verified during periodic inspection.
Practical Example: 20 A Circuit in Australian Conditions
A 20 A general-purpose circuit at 230 V in Sydney (40 °C ambient), 30 m run, cables clipped to surface: Step 1 — Design current = 20 A. Step 2 — At 40 °C ambient (reference temperature for AS/NZS), no temperature derating needed. 2.5 mm² = 24 A ≥ 20 A. Step 3 — Voltage drop: ΔU = 18.1 × 20 × 30 / 1000 = 10.86 V = 4.72%. Under 5% — acceptable. Step 4 — Protection: 20 A MCB, 2.5 mm² cable. If the run were 35 m: ΔU = 12.67 V = 5.5%, exceeding 5%, so upsize to 4 mm² (11 mV/A/m → 7.7 V = 3.3%). Final selection: 2.5 mm² for 30 m, 4 mm² for 35 m.
FAQ
Why does AS/NZS use 40 °C as the reference ambient temperature?
Australia experiences significantly higher average temperatures than Europe (30 °C reference) or North America. Using 40 °C as the base means the published ampacity values already account for typical Australian conditions. In cooler climates within Australia or New Zealand, you can apply correction factors above 1.0 to increase the allowable current.
Can I use NEC or IEC cable sizes in Australia?
No. Australian installations must use cables certified to Australian standards (AS/NZS 5000 series). While the mm² sizes are the same as IEC, the cables must carry the appropriate certification mark. AWG-sized cables from the US are not listed for use under AS/NZS 3000 and would not be accepted by an electrical inspector.
What is the difference between AS/NZS 3000 and AS/NZS 3008.1?
AS/NZS 3000 (Wiring Rules) covers the overall electrical installation requirements — design, protection, earthing, verification. AS/NZS 3008.1 (Selection of cables) is the companion standard specifically for cable sizing — it provides the current-carrying capacity tables, voltage drop values, and derating factors. You need both to properly size cables for an installation.