Ukuran Kabel untuk 150 A 150 Kaki (120V)
| Standar | Ukuran Kabel | Kapasitas Arus | Penurunan Tegangan | Turun % |
| NEC (US) | AWG 3/0 (85 mm²) | 200 A | 3.38 V | 2.82% |
| IEC (EU) | 95 mm² | 223 A | 3.03 V | 2.52% |
| BS (UK) | 70 mm² | 184 A | 4.11 V | 3.42% |
| AS/NZS | 70 mm² | 184 A | 4.11 V | 3.42% |
Tentang AWG 3/0
- Penggunaan umum
- Masukan layanan 165–200A — layanan residensial standar 200A
- Pemutus maks.
- 200 A
- Kelas suhu
- 75 °C
- Referensi NEC
- NEC Table 310.16
Selalu periksa persyaratan kode listrik setempat. Ukuran kabel bergantung pada jenis isolasi, suhu lingkungan, dan pengisian konduit.
Perbandingan Arus Berdekatan
| Arus | AWG | mm² | Kapasitas Arus | Turun % |
| 100 A | AWG 1/0 | 53.5 mm² | 150 A | 2.99% |
| 150 A | AWG 3/0 | 85 mm² | 200 A | 2.82% |
| 200 A | AWG 4/0 | 107.2 mm² | 230 A | 2.98% |
Perbandingan Jarak Berdekatan
| Jarak | AWG | mm² | Kapasitas Arus | Turun % |
| 100 kaki | AWG 1/0 | 53.5 mm² | 150 A | 2.99% |
| 150 kaki | AWG 3/0 | 85 mm² | 200 A | 2.82% |
| 200 kaki | AWG 4/0 | 107.2 mm² | 230 A | 2.98% |