Ukuran Kabel untuk 60 A 75 Kaki (120V)
| Standar | Ukuran Kabel | Kapasitas Arus | Penurunan Tegangan | Turun % |
| NEC (US) | AWG 4 (21.2 mm²) | 85 A | 2.71 V | 2.26% |
| IEC (EU) | 16 mm² | 76 A | 3.59 V | 3.00% |
| BS (UK) | 16 mm² | 76 A | 3.59 V | 3.00% |
| AS/NZS | 16 mm² | 76 A | 3.59 V | 3.00% |
Tentang AWG 4
- Penggunaan umum
- Feeder 70–85A — suplai sub-panel, peralatan komersial
- Pemutus maks.
- 85 A
- Kelas suhu
- 75 °C
- Referensi NEC
- NEC Table 310.16
Selalu periksa persyaratan kode listrik setempat. Ukuran kabel bergantung pada jenis isolasi, suhu lingkungan, dan pengisian konduit.
Perbandingan Arus Berdekatan
| Arus | AWG | mm² | Kapasitas Arus | Turun % |
| 50 A | AWG 4 | 21.2 mm² | 85 A | 1.88% |
| 60 A | AWG 4 | 21.2 mm² | 85 A | 2.26% |
| 100 A | AWG 3 | 26.7 mm² | 100 A | 2.99% |
Perbandingan Jarak Berdekatan
| Jarak | AWG | mm² | Kapasitas Arus | Turun % |
| 50 kaki | AWG 6 | 13.3 mm² | 65 A | 2.40% |
| 75 kaki | AWG 4 | 21.2 mm² | 85 A | 2.26% |
| 100 kaki | AWG 3 | 26.7 mm² | 100 A | 2.39% |